Update Content - 2021-08-27
This commit is contained in:
190
content/inbook/albertos04_decen_decoup_contr.md
Normal file
190
content/inbook/albertos04_decen_decoup_contr.md
Normal file
@@ -0,0 +1,190 @@
|
||||
+++
|
||||
title = "Decentralized and decoupled control"
|
||||
author = ["Thomas Dehaeze"]
|
||||
draft = false
|
||||
+++
|
||||
|
||||
Tags
|
||||
: [Decentralized Control](decentralized_control.md), [Multivariable Control](multivariable_control.md)
|
||||
|
||||
Reference
|
||||
: ([Albertos and Antonio 2004](#org86b8145))
|
||||
|
||||
Author(s)
|
||||
: Albertos, P., & Antonio, S.
|
||||
|
||||
Year
|
||||
: 2004
|
||||
|
||||
|
||||
## Introduction {#introduction}
|
||||
|
||||
Decentralized control is decomposed into two steps:
|
||||
|
||||
1. decoupled the plant into several subsystems
|
||||
2. control the subsystems
|
||||
|
||||
The initial effort of decoupling the system results in subsequent easier design, implementation and tuning.
|
||||
|
||||
Decentralized control tries to control multivariable plants by a suitable decomposition into SISO control loops.
|
||||
If the process has strong coupling or conditioning problems, centralized control may be required.
|
||||
It however requires the availability of a precise model.
|
||||
|
||||
Two approaches can be used to control a coupled system with SISO techniques:
|
||||
|
||||
- **decentralized control** tries to divide the plant and design _independent_ controllers for each subsystems.
|
||||
Two alternative arise:
|
||||
- neglect the coupling
|
||||
- carry out a _decoupling_ operation by "canceling" coupling by transforming the system into a diagonal or triangular structure bia a transformation matrix
|
||||
- **cascade control**
|
||||
|
||||
|
||||
## Mutli-Loop Control, Pairing Selection {#mutli-loop-control-pairing-selection}
|
||||
|
||||
The strategy called _multi-loop control_ consists of first proper input/output pairing, and then design of several SISO controllers.
|
||||
In this way, a complex control problem is divided into several simpler ones.
|
||||
|
||||
The multi-loop control may not work in strongly coupled systems.
|
||||
Therefore, a methodology the access the degree of interaction between the loops is needed.
|
||||
|
||||
|
||||
### [Relative Gain Array](relative_gain_array.md) {#relative-gain-array--relative-gain-array-dot-md}
|
||||
|
||||
The Relative Gain Array (RGA) \\(\Lambda(s)\\) is defined as:
|
||||
|
||||
\begin{equation}
|
||||
\Lambda(s) = G(s) \times (G(s)^T)^{-1}
|
||||
\end{equation}
|
||||
|
||||
The RGA is scaling-independent and controller-independent.
|
||||
These coefficients can be interpreted as the ratio between the open-loop SISO static gain and the gain with "perfect" control on the rest of the loops.
|
||||
|
||||
For demanding control specifications, the values of \\(\Lambda\\) car be drawn as a function of frequency.
|
||||
In this case, at frequencies important for control stability robustness (around the peak of the sensitivity transfer function), if \\(\Lambda(j\omega)\\) approaches the identity matrix, stability problems are avoided in multi-loop control.
|
||||
|
||||
|
||||
## Decoupling {#decoupling}
|
||||
|
||||
In cases when multi-loop control is not effective in reaching the desired specifications, a possible strategy for tackling the MIMO control could be to transform the transfer function matrix into a diagonal dominant one.
|
||||
This strategy is called **decoupling**.
|
||||
|
||||
[Decoupled Control](decoupled_control.md) can be achieved in two ways:
|
||||
|
||||
- feedforward cancellation of the cross-coupling terms
|
||||
- based on state measurements, via a feedback law
|
||||
|
||||
|
||||
### Feedforward Decoupling {#feedforward-decoupling}
|
||||
|
||||
A pre-compensator (Figure [1](#org860681c)) can be added to transform the open-loop characteristics into a new one as chosen by the designer.
|
||||
This decoupler can be taken as the inverse of the plant provided it does not include RHP-zeros.
|
||||
|
||||
<a id="org860681c"></a>
|
||||
|
||||
{{< figure src="/ox-hugo/albertos04_pre_compensator_decoupling.png" caption="Figure 1: Decoupler pre-compensator" >}}
|
||||
|
||||
**Approximate decoupling**:
|
||||
To design low-bandwidth loops, insertion of the inverse DC-gain before the loop ensures decoupling at least at steady-state.
|
||||
If further bandwidth extension is desired, an approximation of \\(G^{-1}\\) valid in low frequencies can be used.
|
||||
|
||||
Although at first glance, decoupling seems an appealing idea, there are some drawbacks:
|
||||
|
||||
- as decoupling is achieved via the coordination of sensors and actuators to achieve an "apparent" diagonal behavior, the failure of one the actuators may heavily affects all loops.
|
||||
- a decoupling design (inverse-based controller) may not be desirable for all disturbance-rejection tasks.
|
||||
- many MIMO non-minimum phase systems, when feedforward decoupled, increase the RHP-zero multiplicity so performance limitations due to its presence are exacerbated.
|
||||
- decoupling may be very sensitive to modeling errors, specially for ill-conditionned plants
|
||||
- feedback decoupling needs full state measurements
|
||||
|
||||
|
||||
### SVD Decoupling {#svd-decoupling}
|
||||
|
||||
A matrix \\(M\\) can be expressed, using the [Singular Value Decomposition](singular_value_decomposition.md) as:
|
||||
|
||||
\begin{equation}
|
||||
M = U \Sigma V^T
|
||||
\end{equation}
|
||||
|
||||
where \\(U\\) and \\(V\\) are orthogonal matrices and \\(\Sigma\\) is diagonal.
|
||||
|
||||
The SVD can be used to obtain decoupled equations between linear combinations of sensors and linear combinations of actuators.
|
||||
In this way, although losing part of its intuitive sense, a decoupled design can be carried out even for non-square plants.
|
||||
|
||||
If sensors are multiplied by \\(U^T\\) and control actions multiplied by \\(V\\), as in Figure [2](#orgbb644a3), then the loop, in the transformed variables, is decoupled, so a diagonal controller \\(K\_D\\) can be used.
|
||||
Usually, the sensor and actuator transformations are obtained using the DC gain, or a real approximation of \\(G(j\omega)\\), where \\(\omega\\) is around the desired closed-loop bandwidth.
|
||||
|
||||
<a id="orgbb644a3"></a>
|
||||
|
||||
{{< figure src="/ox-hugo/albertos04_svd_decoupling.png" caption="Figure 2: SVD decoupling: \\(K\_D\\) is a diagonal controller designed for \\(\Sigma\\)" >}}
|
||||
|
||||
The transformed sensor-actuator pair corresponding to the maximum singular value is the direction with biggest "gain" on the plant, that is, the combination of variables being "easiest to control".
|
||||
|
||||
In ill-conditioned plants, the ratio between the biggest and lower singular value is large (for reference, greater than 20).
|
||||
They are very sensitive to input uncertainty as some "input directions" have much bigger gain than other ones.
|
||||
|
||||
SVD decoupling produces the most suitable combinations for independent "multi-loop" control in the transformed variables, so its performance may be better than RGA-based design (at the expense of losing physical interpretability).
|
||||
If some of the vectors in \\(V\\) (input directions) have a significant component on a particular input, and the corresponding output direction is also significantly pointing to a particular output, that combination is a good candidate for an independent multi-loop control.
|
||||
|
||||
|
||||
## Conclusions {#conclusions}
|
||||
|
||||
In this chapter, the control of systems with multiple inputs and outputs is discussed using SISO-based tools, either directly or after some multivariable decoupling transformations.
|
||||
|
||||
Multi-loop strategies, if suitable, may present th advantages of fault tolerance, as well as simplicity.
|
||||
However, in some cases, tuning may be difficult and coupling may severely limit their performance.
|
||||
|
||||
Decoupling is based on mathematical transformations of the system models into diagonal form.
|
||||
Feedforward decoupling can be used in many cases.
|
||||
Feedback decoupling achieves its objective if state is measurable and system is minimum-phase.
|
||||
However, decoupling may be very sensitive to modelling errors and it is not the optimal strategy for disturbance rejection.
|
||||
|
||||
Cascade control is widely used in industry to improve the behaviour of basic SISO loops via the addition of extra sensors and actuators.
|
||||
However, ease of tuning requires that different time constants are involved in different subsystems.
|
||||
In general, addition of extra sensors and actuators in a SISO or MIMO loop, will improve achievable performance and/or tolerance to modelling errors.
|
||||
The level of improvement must be traded off against the cost of additional instrumentation.
|
||||
|
||||
|
||||
## Implementation and Other Issues {#implementation-and-other-issues}
|
||||
|
||||
There are two main categories for the implementation of MIMO control:
|
||||
|
||||
- Decentralized, Decoupled, Cascade
|
||||
- Centralized, optimization based
|
||||
|
||||
A fundamental reason to use cascade and decentralized control in most practical applications is because they require less modelling effort.
|
||||
Other advantages of cascade and decentralized control are:
|
||||
|
||||
- its behaviour can be easily understood
|
||||
- standard equipment can be used (PID controllers, etc.)
|
||||
- their decoupled behavior enables easier tuning with model-free strategies
|
||||
- decentralized implementation tends to be more fault-tolerant, as individual loops will try to keep their set-points even in the case some other components have failed.
|
||||
|
||||
|
||||
### [Anti-Windup Control](anti_windup_control.md) {#anti-windup-control--anti-windup-control-dot-md}
|
||||
|
||||
In practice, it is possible that an actuator saturate.
|
||||
In such case, the feedback path is broken, and this has several implications:
|
||||
|
||||
- unstable processes: the process output might go out of control
|
||||
- multi-loop and centralized control: even with stable plants, opening a feedback path may cause the overall loop to become unstable
|
||||
|
||||
The wind-up problem can appear with integral action regulators: during significative step changes in the set point, the integral of the error keeps accumulation and when reaching the desired set-point the accumulated integral action produces a significant overshoot increment.
|
||||
In SISO PID regulators, anti-windup schemes are implemented by either stopping integration if the actuator is saturated or by implementing the following control law:
|
||||
|
||||
\begin{equation}
|
||||
u = K(r - y) - K T\_D \frac{dy}{dt} + \int K T\_i^{-1} (r - y) + T\_t^{-1} (u\_m - u) dt \label{eq:antiwindup\_pid}
|
||||
\end{equation}
|
||||
|
||||
where \\(u\\) is the calculated control action and \\(u\_m\\) is the actual control action applied to the plant.
|
||||
In non-saturated behaviour, \\(u=u\_m\\) and the equation is the ordinary PID.
|
||||
In saturation, \\(u\_m\\) is a constant and the resulting equations drive \\(u\\) down towards \\(u\_m\\) dynamically, with time constant \\(T\_T\\).
|
||||
|
||||
|
||||
### [Bumpless Transfer](bumpless_transfer.md) {#bumpless-transfer--bumpless-transfer-dot-md}
|
||||
|
||||
When switching on the regulator, significant transient behavior can be seen and the controller may saturate the actuators.
|
||||
The solution is similar to that of the wind-up phenomenon: the regulator should be always on, carrying out calculations by using \eqref{eq:antiwindup_pid}.
|
||||
|
||||
|
||||
## Bibliography {#bibliography}
|
||||
|
||||
<a id="org86b8145"></a>Albertos, P., and S. Antonio. 2004. “Decentralized and Decoupled Control.” In _Multivariable Control Systems: An Engineering Approach_, 125–62. Advanced Textbooks in Control and Signal Processing. Springer-Verlag. <https://doi.org/10.1007/b97506>.
|
236
content/inbook/levine11_contr_system_applic.md
Normal file
236
content/inbook/levine11_contr_system_applic.md
Normal file
@@ -0,0 +1,236 @@
|
||||
+++
|
||||
title = "Advanced Motion Control Design"
|
||||
author = ["Thomas Dehaeze"]
|
||||
draft = false
|
||||
+++
|
||||
|
||||
Tags
|
||||
:
|
||||
|
||||
|
||||
Reference
|
||||
: ([Levine 2011](#orgb7728f4)), chapter 27
|
||||
|
||||
Author(s)
|
||||
: Levine, W. S.
|
||||
|
||||
Year
|
||||
: 2011
|
||||
|
||||
|
||||
## Introduction {#introduction}
|
||||
|
||||
The industrial state of the art control of motion systems can be summarized as follows.
|
||||
Most systems, by design, are either decoupled, or can be decoupled using static input-output transformations.
|
||||
Hence, most motion systems and their motion software architecture use SISO control design methods and solutions.
|
||||
|
||||
Feedback design is mostly done in the frequency domain, using [Loop-Shaping](loop_shaping.md) techniques.
|
||||
A typical motion controller has a PID structure, with a low pass at high frequencies and one or two notch filters to compensate flexible dynamics.
|
||||
In addition to the feedback controller, a feedforward controller is applied with acceleration, velocity from the reference signal.
|
||||
|
||||
The setpoint itself is a result of a setpoint generator with jerk limitation profiles (see [Trajectory Generation](trajectory_generation.md)).
|
||||
If the requirements increase, the dynamic coupling between the various DOFs can no longer be neglected and more advanced MIMO control is required.
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
Centralized control
|
||||
: the transfer function matrix of the controller is allowed to have any structure
|
||||
|
||||
Decentralized control
|
||||
: diagonal controller transfer function, but constant decoupling manipulations of inputs and outputs are allowed
|
||||
|
||||
Independent decentralized control
|
||||
: a single loop is designed without taking into account the effect of earlier or later designed loops
|
||||
|
||||
Sequential decentralized control
|
||||
: a single loop is designed with taking into account the effect of all earlier closed loops
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
## Motion Systems {#motion-systems}
|
||||
|
||||
Here, we focus on the control of linear time invariant electromechanical motion systems that have the same number of actuators and sensors as Rigid Body modes.
|
||||
The dynamics of such systems are often dominated by the mechanics, such that:
|
||||
|
||||
\begin{equation}
|
||||
G\_p(s) = \sum\_{i=1}^{N\_{rb}} \frac{c\_i b\_i^T}{s^2} + \sum\_{i=N\_{rb} + 1}^{N} \frac{c\_ib\_i^T}{s^2 + 2 \xi\_i \omega\_i s + \omega\_i^2}
|
||||
\end{equation}
|
||||
|
||||
with \\(N\_{rb}\\) is the number of rigid body modes.
|
||||
The vectors \\(c\_i,b\_i\\) span the directions of the ith mode shapes.
|
||||
|
||||
If the resonance frequencies \\(\omega\_i\\) are high enough, the plant can be approximately decoupled using static input/output transformations \\(T\_u,T\_y\\) so that:
|
||||
|
||||
\begin{equation}
|
||||
G\_{yu} = T\_y G\_p(s) T\_u = \frac{1}{s^2} \begin{bmatrix}
|
||||
m & 0 & & \dots & & 0 \\\\\\
|
||||
0 & m & & & & \\\\\\
|
||||
& & m & \ddots & & \vdots \\\\\\
|
||||
\vdots & & \ddots & I\_x & & \\\\\\
|
||||
& & & & I\_y & 0 \\\\\\
|
||||
0 & & \dots & & 0 & I\_z
|
||||
\end{bmatrix} + G\_{\text{flex}}(s)
|
||||
\end{equation}
|
||||
|
||||
|
||||
## Feedback Control Design {#feedback-control-design}
|
||||
|
||||
|
||||
### [Loop-Shaping](loop_shaping.md) - The SISO case {#loop-shaping--loop-shaping-dot-md--the-siso-case}
|
||||
|
||||
The key idea of loopshaping is the modification of the controller such that the open-loop is made according to specifications.
|
||||
The reason this works well is that the controller enters linearly into the open-loop transfer function \\(L(s) = G(s)K(s)\\).
|
||||
However, in practice all specifications are of course given in terms of the final system performance, that is, as _closed-loop_ specifications.
|
||||
So we should convert the closed-loop specifications into specifications on the open-loop.
|
||||
|
||||
Take as an example the simple case of a disturbance being a sinusoid of known amplitude and frequency.
|
||||
If we know the specifications on the error amplitude, we can derive the requirement on the process sensitivity at that frequency.
|
||||
Since at low frequency the sensitivity can be approximated as the inverse of the open-loop, we can translate this into a specification of the open-loop at that frequency.
|
||||
Because we know that the slope of the open-loop of a well tuned motion system will be between -2 and -1, we can estimate the required crossover frequency.
|
||||
|
||||
|
||||
### Loop-Shaping - The MIMO case {#loop-shaping-the-mimo-case}
|
||||
|
||||
In MIMO systems, it is much less trivial to apply loopshaping.
|
||||
The stability is determined by the closed-loop polynomial, \\(\det(I + L(s))\\), and the characteristic loci (eigenvalues of the FRF \\(L(j\omega)\\) in the complex plane) can be used for this graphically.
|
||||
A system with N inputs and N outputs has N characteristic loci.
|
||||
|
||||
If each eigen value locus does not encircle the point (-1,0), the MIMO system is closed-loop stable.
|
||||
The shaping of these eigenvalue loci is not straightforward if the plant has large off-diagonal elements.
|
||||
In that case, a single element of the controller will affect more eigenvalue loci.
|
||||
|
||||
The strong non-intuitive aspect of MIMO loopshaping and the fact that SISO loopshaping is used often, are major obstacles in application of modern design tools in industrial motion systems.
|
||||
|
||||
<div class="important">
|
||||
<div></div>
|
||||
|
||||
For that reason, the step-by-step approach is proposed:
|
||||
|
||||
1. Interaction Analysis
|
||||
2. Decoupling Transformations
|
||||
3. Independent SISO design
|
||||
4. Sequential SISO design
|
||||
5. Norm-based MIMO design
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
#### Interaction Analysis {#interaction-analysis}
|
||||
|
||||
The goal of the interaction analysis is to identify two-sided interactions in the plant dynamics.
|
||||
Two measured for plant interactions can be used:
|
||||
|
||||
- Relative Gain Array (RGA) per frequency
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
The frequency dependent relative gain array is calculated as:
|
||||
|
||||
\begin{equation}
|
||||
\text{RGA}(G(j\omega)) = G(j\omega) \times (G(j\omega)^{-1})^{T}
|
||||
\end{equation}
|
||||
|
||||
where \\(\times\\) denotes element wise multiplication.
|
||||
|
||||
</div>
|
||||
- Structure Singular Value (SSV) of interaction as multiplicative output uncertainty
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
The structured singular value interaction measure is the following condition:
|
||||
|
||||
\begin{equation}
|
||||
\mu\_D(E\_T(j\omega)) < \frac{1}{2}, \forall \omega
|
||||
\end{equation}
|
||||
|
||||
with \\(E\_T(j\omega) = G\_{nd}(j\omega) G\_d^{-1}(j\omega)\\), \\(\mu\_D\\) is the structured singular value, with respect to the diagonal structure of the feedback controller.
|
||||
\\(G\_d(s)\\) are the diagonal terms of the transfer function matrix, and \\(G\_{nd}(s) = G(s) - G\_d(s)\\).
|
||||
|
||||
If a diagonal transfer function matrix is used, controllers gains must be small at frequencies where this condition is not met.
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
#### Decoupling Transformations {#decoupling-transformations}
|
||||
|
||||
A common method to reduce plant interaction is to redefine the input and output of the plant.
|
||||
One can combine several inputs or outputs to control the system in more decoupled coordinates.
|
||||
For motion systems most of these transformations are found on the basis of _kinematic models_.
|
||||
Herein, combinations of the actuators are defined so that actuator variables act in independent (orthogonal) directions at the center of gravity.
|
||||
Likewise, combinations of the sensors are defined so that each translation and rotation of the center of gravity can be measured independently.
|
||||
This is basically the inversion of a kinematic model of the plant.
|
||||
|
||||
As motion systems are often designed to be light and stiff, kinematic decoupling is often sufficient to achieve acceptable decoupling at the crossover frequency.
|
||||
|
||||
|
||||
#### Independent SISO design {#independent-siso-design}
|
||||
|
||||
For systems where interaction is low, or the decoupling is almost successful, one can design a _diagonal_ controller by closing each control loop independently.
|
||||
The residual interaction can be accounted for in the analysis.
|
||||
|
||||
For this, we make use of the following decomposition:
|
||||
|
||||
\begin{equation}
|
||||
\det(I + GK) = \det(I + E\_T T\_d) \det(I + G\_d K)
|
||||
\end{equation}
|
||||
|
||||
with \\(T\_d = G\_d K (I + G\_d K)^{-1}\\).
|
||||
\\(G\_d(s)\\) is defined to be only the diagonal terms of the plant transfer function matrix.
|
||||
The effect of the non-diagonal terms of the plant \\(G\_{nd}(s) = G(s) - G\_d(s)\\) is accounted for in \\(E\_T(s)\\).
|
||||
|
||||
<div class="important">
|
||||
<div></div>
|
||||
|
||||
Then the MIMO closed-loop stability assessment can be slit up in two assessments:
|
||||
|
||||
- the first for stability of N non-interacting loops, namely \\(\det(I + G\_d(s)K(s))\\)
|
||||
- the second for stability of \\(\det(I + E\_T(s)T\_d(s))\\)
|
||||
|
||||
</div>
|
||||
|
||||
If \\(G(s)\\) and \\(T\_d(s)\\) are stable, one can use the _small gain theorem_ to find a sufficient condition of stability of \\(\det(I + E\_TT\_d)\\) as
|
||||
|
||||
\begin{equation}
|
||||
\rho(E\_T(j\omega) T\_d(j\omega)) < 1, \forall \omega
|
||||
\end{equation}
|
||||
|
||||
where \\(\rho\\) is the spectral radius.
|
||||
|
||||
Due to the fact that a sufficient condition is used, independent loop closing usually leads to conservative designs.
|
||||
|
||||
|
||||
#### Sequential SISO design {#sequential-siso-design}
|
||||
|
||||
If the interaction is larger, the sequential loop closing method is appropriate.
|
||||
The controller is still a diagonal transfer function matrix, but each control designs are now dependent.
|
||||
In principle, one starts with the open-loop FRF of the MIMO Plant.
|
||||
Then one loop is closed using SISO loopshaping.
|
||||
The controller is taken into the plant description, and a new FRF is obtained with one input and output less.
|
||||
Then, the next loop is designed and so on.
|
||||
|
||||
The multivariable system is nominally closed-loop stable if in each design step the system is closed-loop stable.
|
||||
However, the robustness margins in each design step do not guarantee robust stability of the final multivariable system.
|
||||
|
||||
Drawbacks of sequential design are:
|
||||
|
||||
- the ordering of the design steps may have great impact on the achievable performance.
|
||||
There is no general approach to determine the best sequence.
|
||||
- there are no guarantees that robustness margins in earlier loops are preserved.
|
||||
- as each design step usually considers only a single output, the responses in earlier designed loops may degrade.
|
||||
|
||||
|
||||
#### Norm-based MIMO design {#norm-based-mimo-design}
|
||||
|
||||
If sequential SISO design is not successful, the next step is to start norm-based control design.
|
||||
This method requires a parametric model and weighting filters to express the control problem in terms of an operator norm like \\(H\_2\\) or \\(H\_\infty\\).
|
||||
|
||||
Parametric models are usually build up step-by-step, first considering the unmodeled dynamics as (unstructured) uncertainty.
|
||||
|
||||
|
||||
## Bibliography {#bibliography}
|
||||
|
||||
<a id="orgb7728f4"></a>Levine, W. S. 2011. _Control System Applications_. The Control Handbook. Boca Raton: CRC Press.
|
236
content/inbook/steinbuch11_advan_motion_contr_desig.md
Normal file
236
content/inbook/steinbuch11_advan_motion_contr_desig.md
Normal file
@@ -0,0 +1,236 @@
|
||||
+++
|
||||
title = "Advanced Motion Control Design"
|
||||
author = ["Thomas Dehaeze"]
|
||||
draft = false
|
||||
+++
|
||||
|
||||
Tags
|
||||
:
|
||||
|
||||
|
||||
Reference
|
||||
: ([Steinbuch et al. 2011](#org16dd9d1))
|
||||
|
||||
Author(s)
|
||||
: Steinbuch, M., Merry, R., Boerlage, M., Ronde, M., & Molengraft, M.
|
||||
|
||||
Year
|
||||
: 2011
|
||||
|
||||
|
||||
## Introduction {#introduction}
|
||||
|
||||
The industrial state of the art control of motion systems can be summarized as follows.
|
||||
Most systems, by design, are either decoupled, or can be decoupled using static input-output transformations.
|
||||
Hence, most motion systems and their motion software architecture use SISO control design methods and solutions.
|
||||
|
||||
Feedback design is mostly done in the frequency domain, using [Loop-Shaping](loop_shaping.md) techniques.
|
||||
A typical motion controller has a PID structure, with a low pass at high frequencies and one or two notch filters to compensate flexible dynamics.
|
||||
In addition to the feedback controller, a feedforward controller is applied with acceleration, velocity from the reference signal.
|
||||
|
||||
The setpoint itself is a result of a setpoint generator with jerk limitation profiles (see [Trajectory Generation](trajectory_generation.md)).
|
||||
If the requirements increase, the dynamic coupling between the various DOFs can no longer be neglected and more advanced MIMO control is required.
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
Centralized control
|
||||
: the transfer function matrix of the controller is allowed to have any structure
|
||||
|
||||
Decentralized control
|
||||
: diagonal controller transfer function, but constant decoupling manipulations of inputs and outputs are allowed
|
||||
|
||||
Independent decentralized control
|
||||
: a single loop is designed without taking into account the effect of earlier or later designed loops
|
||||
|
||||
Sequential decentralized control
|
||||
: a single loop is designed with taking into account the effect of all earlier closed loops
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
## Motion Systems {#motion-systems}
|
||||
|
||||
Here, we focus on the control of linear time invariant electromechanical motion systems that have the same number of actuators and sensors as Rigid Body modes.
|
||||
The dynamics of such systems are often dominated by the mechanics, such that:
|
||||
|
||||
\begin{equation}
|
||||
G\_p(s) = \sum\_{i=1}^{N\_{rb}} \frac{c\_i b\_i^T}{s^2} + \sum\_{i=N\_{rb} + 1}^{N} \frac{c\_ib\_i^T}{s^2 + 2 \xi\_i \omega\_i s + \omega\_i^2}
|
||||
\end{equation}
|
||||
|
||||
with \\(N\_{rb}\\) is the number of rigid body modes.
|
||||
The vectors \\(c\_i,b\_i\\) span the directions of the ith mode shapes.
|
||||
|
||||
If the resonance frequencies \\(\omega\_i\\) are high enough, the plant can be approximately decoupled using static input/output transformations \\(T\_u,T\_y\\) so that:
|
||||
|
||||
\begin{equation}
|
||||
G\_{yu} = T\_y G\_p(s) T\_u = \frac{1}{s^2} \begin{bmatrix}
|
||||
m & 0 & & \dots & & 0 \\\\\\
|
||||
0 & m & & & & \\\\\\
|
||||
& & m & \ddots & & \vdots \\\\\\
|
||||
\vdots & & \ddots & I\_x & & \\\\\\
|
||||
& & & & I\_y & 0 \\\\\\
|
||||
0 & & \dots & & 0 & I\_z
|
||||
\end{bmatrix} + G\_{\text{flex}}(s)
|
||||
\end{equation}
|
||||
|
||||
|
||||
## Feedback Control Design {#feedback-control-design}
|
||||
|
||||
|
||||
### [Loop-Shaping](loop_shaping.md) - The SISO case {#loop-shaping--loop-shaping-dot-md--the-siso-case}
|
||||
|
||||
The key idea of loopshaping is the modification of the controller such that the open-loop is made according to specifications.
|
||||
The reason this works well is that the controller enters linearly into the open-loop transfer function \\(L(s) = G(s)K(s)\\).
|
||||
However, in practice all specifications are of course given in terms of the final system performance, that is, as _closed-loop_ specifications.
|
||||
So we should convert the closed-loop specifications into specifications on the open-loop.
|
||||
|
||||
Take as an example the simple case of a disturbance being a sinusoid of known amplitude and frequency.
|
||||
If we know the specifications on the error amplitude, we can derive the requirement on the process sensitivity at that frequency.
|
||||
Since at low frequency the sensitivity can be approximated as the inverse of the open-loop, we can translate this into a specification of the open-loop at that frequency.
|
||||
Because we know that the slope of the open-loop of a well tuned motion system will be between -2 and -1, we can estimate the required crossover frequency.
|
||||
|
||||
|
||||
### Loop-Shaping - The MIMO case {#loop-shaping-the-mimo-case}
|
||||
|
||||
In MIMO systems, it is much less trivial to apply loopshaping.
|
||||
The stability is determined by the closed-loop polynomial, \\(\det(I + L(s))\\), and the characteristic loci (eigenvalues of the FRF \\(L(j\omega)\\) in the complex plane) can be used for this graphically.
|
||||
A system with N inputs and N outputs has N characteristic loci.
|
||||
|
||||
If each eigen value locus does not encircle the point (-1,0), the MIMO system is closed-loop stable.
|
||||
The shaping of these eigenvalue loci is not straightforward if the plant has large off-diagonal elements.
|
||||
In that case, a single element of the controller will affect more eigenvalue loci.
|
||||
|
||||
The strong non-intuitive aspect of MIMO loopshaping and the fact that SISO loopshaping is used often, are major obstacles in application of modern design tools in industrial motion systems.
|
||||
|
||||
<div class="important">
|
||||
<div></div>
|
||||
|
||||
For that reason, the step-by-step approach is proposed:
|
||||
|
||||
1. Interaction Analysis
|
||||
2. Decoupling Transformations
|
||||
3. Independent SISO design
|
||||
4. Sequential SISO design
|
||||
5. Norm-based MIMO design
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
#### Interaction Analysis {#interaction-analysis}
|
||||
|
||||
The goal of the interaction analysis is to identify two-sided interactions in the plant dynamics.
|
||||
Two measured for plant interactions can be used:
|
||||
|
||||
- Relative Gain Array (RGA) per frequency
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
The frequency dependent relative gain array is calculated as:
|
||||
|
||||
\begin{equation}
|
||||
\text{RGA}(G(j\omega)) = G(j\omega) \times (G(j\omega)^{-1})^{T}
|
||||
\end{equation}
|
||||
|
||||
where \\(\times\\) denotes element wise multiplication.
|
||||
|
||||
</div>
|
||||
- Structure Singular Value (SSV) of interaction as multiplicative output uncertainty
|
||||
|
||||
<div class="definition">
|
||||
<div></div>
|
||||
|
||||
The structured singular value interaction measure is the following condition:
|
||||
|
||||
\begin{equation}
|
||||
\mu\_D(E\_T(j\omega)) < \frac{1}{2}, \forall \omega
|
||||
\end{equation}
|
||||
|
||||
with \\(E\_T(j\omega) = G\_{nd}(j\omega) G\_d^{-1}(j\omega)\\), \\(\mu\_D\\) is the structured singular value, with respect to the diagonal structure of the feedback controller.
|
||||
\\(G\_d(s)\\) are the diagonal terms of the transfer function matrix, and \\(G\_{nd}(s) = G(s) - G\_d(s)\\).
|
||||
|
||||
If a diagonal transfer function matrix is used, controllers gains must be small at frequencies where this condition is not met.
|
||||
|
||||
</div>
|
||||
|
||||
|
||||
#### Decoupling Transformations {#decoupling-transformations}
|
||||
|
||||
A common method to reduce plant interaction is to redefine the input and output of the plant.
|
||||
One can combine several inputs or outputs to control the system in more decoupled coordinates.
|
||||
For motion systems most of these transformations are found on the basis of _kinematic models_.
|
||||
Herein, combinations of the actuators are defined so that actuator variables act in independent (orthogonal) directions at the center of gravity.
|
||||
Likewise, combinations of the sensors are defined so that each translation and rotation of the center of gravity can be measured independently.
|
||||
This is basically the inversion of a kinematic model of the plant.
|
||||
|
||||
As motion systems are often designed to be light and stiff, kinematic decoupling is often sufficient to achieve acceptable decoupling at the crossover frequency.
|
||||
|
||||
|
||||
#### Independent SISO design {#independent-siso-design}
|
||||
|
||||
For systems where interaction is low, or the decoupling is almost successful, one can design a _diagonal_ controller by closing each control loop independently.
|
||||
The residual interaction can be accounted for in the analysis.
|
||||
|
||||
For this, we make use of the following decomposition:
|
||||
|
||||
\begin{equation}
|
||||
\det(I + GK) = \det(I + E\_T T\_d) \det(I + G\_d K)
|
||||
\end{equation}
|
||||
|
||||
with \\(T\_d = G\_d K (I + G\_d K)^{-1}\\).
|
||||
\\(G\_d(s)\\) is defined to be only the diagonal terms of the plant transfer function matrix.
|
||||
The effect of the non-diagonal terms of the plant \\(G\_{nd}(s) = G(s) - G\_d(s)\\) is accounted for in \\(E\_T(s)\\).
|
||||
|
||||
<div class="important">
|
||||
<div></div>
|
||||
|
||||
Then the MIMO closed-loop stability assessment can be slit up in two assessments:
|
||||
|
||||
- the first for stability of N non-interacting loops, namely \\(\det(I + G\_d(s)K(s))\\)
|
||||
- the second for stability of \\(\det(I + E\_T(s)T\_d(s))\\)
|
||||
|
||||
</div>
|
||||
|
||||
If \\(G(s)\\) and \\(T\_d(s)\\) are stable, one can use the _small gain theorem_ to find a sufficient condition of stability of \\(\det(I + E\_TT\_d)\\) as
|
||||
|
||||
\begin{equation}
|
||||
\rho(E\_T(j\omega) T\_d(j\omega)) < 1, \forall \omega
|
||||
\end{equation}
|
||||
|
||||
where \\(\rho\\) is the spectral radius.
|
||||
|
||||
Due to the fact that a sufficient condition is used, independent loop closing usually leads to conservative designs.
|
||||
|
||||
|
||||
#### Sequential SISO design {#sequential-siso-design}
|
||||
|
||||
If the interaction is larger, the sequential loop closing method is appropriate.
|
||||
The controller is still a diagonal transfer function matrix, but each control designs are now dependent.
|
||||
In principle, one starts with the open-loop FRF of the MIMO Plant.
|
||||
Then one loop is closed using SISO loopshaping.
|
||||
The controller is taken into the plant description, and a new FRF is obtained with one input and output less.
|
||||
Then, the next loop is designed and so on.
|
||||
|
||||
The multivariable system is nominally closed-loop stable if in each design step the system is closed-loop stable.
|
||||
However, the robustness margins in each design step do not guarantee robust stability of the final multivariable system.
|
||||
|
||||
Drawbacks of sequential design are:
|
||||
|
||||
- the ordering of the design steps may have great impact on the achievable performance.
|
||||
There is no general approach to determine the best sequence.
|
||||
- there are no guarantees that robustness margins in earlier loops are preserved.
|
||||
- as each design step usually considers only a single output, the responses in earlier designed loops may degrade.
|
||||
|
||||
|
||||
#### Norm-based MIMO design {#norm-based-mimo-design}
|
||||
|
||||
If sequential SISO design is not successful, the next step is to start norm-based control design.
|
||||
This method requires a parametric model and weighting filters to express the control problem in terms of an operator norm like \\(H\_2\\) or \\(H\_\infty\\).
|
||||
|
||||
Parametric models are usually build up step-by-step, first considering the unmodeled dynamics as (unstructured) uncertainty.
|
||||
|
||||
|
||||
## Bibliography {#bibliography}
|
||||
|
||||
<a id="org16dd9d1"></a>Steinbuch, Maarten, Roel Merry, Matthijs Boerlage, Michael Ronde, and Marinus Molengraft. 2011. “Advanced Motion Control Design.” In _Control System Applications_, 651–76. CRC Press.
|
Reference in New Issue
Block a user