@@ -22,16 +22,16 @@ In order to implement anti-windup, the integrator usually has to be **explicit**
This is one of the reasons why the PID controller is so useful: the integral action is clearly separated from the other terms.
### Anti-windup strategies {#anti-windup-strategies}
## Anti-windup strategies {#anti-windup-strategies}
#### Conditional integration (integrator clamping) {#conditional-integration--integrator-clamping}
### Conditional integration (integrator clamping) {#conditional-integration--integrator-clamping}
The integrator is simply stopped (or reset) when the actuator is saturated.
For instance, the integration is frozen as long as \\(u \neq \text{sat}(u)\\), possibly only if the error would further increase the saturation (i.e. same sign of \\(u\\) and \\(e\\)).
#### Back-calculation {#back-calculation}
### Back-calculation {#back-calculation}
The difference between the saturated and the requested control signal, \\(e\_s = \text{sat}(u) - u\\), is fed back to the integrator input through a gain \\(1/T\_t\\):
@@ -42,9 +42,3 @@ The difference between the saturated and the requested control signal, \\(e\_s =
When there is no saturation, \\(e\_s = 0\\) and the controller behaves as usual.
When saturated, the integrator state is driven so that \\(u\\) tracks the saturation limit.
The tracking time constant \\(T\_t\\) sets how fast the integrator is unwound (a common choice is \\(T\_t = \sqrt{T\_i T\_d}\\) or \\(T\_t = T\_i\\)).